| Customization: | Available |
|---|---|
| Grounding: | Standard Grounding |
| Shell Material: | Sheet Metal |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency

| Category | Parameter | Specification | Verification |
|---|---|---|---|
| Power Input | Voltage / Frequency | 200-240V AC ±15% / 50-60Hz ±3Hz | IEC 62040-3 |
| Connectors | Dual IEC 60320 C20 (16A per input) | UL 498 Certified | |
| Power Output | High-Power Ports | 2× C19 (16A each) | Max 3,680W per port |
| Branch Ports | 6× C13 (10A each) | Total capacity: 3.8kVA | |
| Switching | Transfer Time | ≤4ms | Oscilloscope verified |
| Transfer Conditions | >15% voltage deviation / >±0.5Hz freq. error / Manual override | Zero-crossing detection | |
| Monitoring | Parameters | Voltage, Current, kW/kVA/kVAR, PF, Frequency, Energy (kWh) | ±0.5% accuracy |
| Sampling Rate | 128 samples/cycle | Real-time waveform capture | |
| Communication | Protocols | SNMP v3, Modbus-TCP/RTU, SSH, Telnet, Custom TCP | TLS 1.2 encrypted |
| Ports | 1× RS485 (cascading), 1× USB (firmware), RJ45 (10/100M Ethernet) | Supports ≤32 cascaded units | |
| Control | Load Management | Per-output remote ON/OFF + Sequential startup | Web/CLI interface |
| User Access | Admin/Operator/Viewer roles with audit logging | RBAC support | |
| Protection | Electrical Safety | 6kV surge suppression / 10kA SCCR / Input OVP-UVP | UL 1008, EN 61643-11 |
| Mechanical | Form Factor | 1U Rack-mountable (44H × 483W × 260D mm) | Steel enclosure, IP20 |
| Cooling | Dual independent fan modules (N+1 redundancy) | Hot-swappable | |
| Environmental | Operating Temp | 0°C to 40°C (derate 2.5%/°C above 35°C) | IEC 62040-1 |
| Compliance | Standards | IEC 62040, UL 1008, CE, RoHS, EN 55032 Class A (EMC) | Full test repo |






| Advantage | Technical Impact | Customer Value |
|---|---|---|
| Zero Downtime Transfer | ≤4ms solid-state switching between sources (<1° phase sync) | Prevents IT reboots, medical device shutdowns |
| Dual-Module Design | Isolated output banks: Module A (1C19+3C13) + Module B (1C19+3C13) | Fault containment; maintenance without full shutdown |
| Precision Monitoring | ±0.5% metering with 128 samples/cycle | Enables predictive maintenance & PUE optimization |
| Control Integration | SNMP traps + Modbus-TCP/BMS integration + Email/SMS alerts | Unified DCIM control; SLA compliance reporting |
| High-Density Power | 3.8kVA total (2×16A C19 + 6×10A C13) in 1U space | 40% more outlets vs competitors; reduces rack footprint |