Customization: | Available |
---|---|
Grounding: | Standard Grounding |
Shell Material: | Sheet Metal |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Input Voltage
|
3Phase 380VAc -480VAC
|
Input Current
|
125A
|
Model Number
|
OIT-12PA45-MCB-3P-125A-A
|
Protection
|
4*3P 40A Hydraulic circuit breaker
|
AC outlets quantity
|
12 bits/ options
|
Socket
|
PA45 socket
|
Output
|
3 phases:380-480VAC;1 phases:220-277VAC
|
Maximum load current
|
3 phases Max 125A per phase
|
Neutral
wire Current alarm |
When the Neutral line current exceeds 10A, the first indicator light will light up
|
|
When the Neutral line current exceeds 20A, the Second indicator light will light up
|
|
When the Neutral line current exceeds 40A, the third indicator light will light up
|
|
When the Neutral line current exceeds 60A, the fourth indicator light will light up
|
Standard
|
Compliant to U L /ETL/CE
|
Grounding
|
Standard grounding
|
Color
|
Customized
|
Size
|
Customized
|
Material
|
Sheet metal
|